Data center liquid cooling vendors, spec by spec

Data center liquid cooling comes in four product families: coolant distribution units (CDUs), direct-to-chip cold plates, immersion tanks and rear-door heat exchangers. This table tracks 46 vendors. Shipping CDUs run from 13 kW (GRC ICEraQ NANO) to 8,150 kW (DCX Liquid Cooling Systems FDU V2AT2), and CoolIT, Vertiv, Motivair and Boyd Thermal each ship units of 2.3 MW or more. Every rating links to the vendor’s datasheet or release.

46 vendors 137 sources, each dated Checked

Liquid cooling loop, drawn as a P&ID Facility water at 32 °C enters the CDU heat exchanger. The CDU pumps the technology cooling system loop out at 36 °C to cold plates on a GPU tray; the heated return flows back to the CDU. Facility water supply Facility water return TT 01 32 °C CDU CDU: heat exchanger, pump, strainer TT 02 36 °C TCS supply GPU GPU GPU GPU tray, cold plates TCS return
The approach is the gap between the two readings: 4 K at STULZ’s CyberCool rating point of 32 °C facility water and 36 °C supply (STULZ, checked 9 Nov 2026).
TechnologiesGPU platforms (vendor-stated)LevelCoolant
DCX Liquid Cooling Systems60038,1502CDU · IMM-1φ · Manifold · FluidNVIDIA GB200 NVL72; NVIDIA GB300 NVL72; NVIDIA Vera RubinIn-rack, In-row, FacilityWG · DE-1φ—Europe2026-11-09
Carrier1,30035,0003CDU—In-row, FacilityWG—North America2026-11-09
Supermicro10025,0001CDU · D2C · Sidecar · Manifold · OEMNVIDIA GB200 NVL72; NVIDIA HGX B300; AMD Instinct MI300X/MI325X; AMD Instinct MI300AServer, In-rack, In-rowWG—North America2026-11-09
CoolIT Systems8043,0001CDU · D2C · Sidecar · ManifoldNVIDIA Vera Rubin (CHx3000); AMD Helios (CHx3000); NVIDIA GB200 NVL72 (CHx2000: up to twelve 120 kW racks)Server, In-rack, In-row, FacilityWGEcolabNorth America2026-11-09
Cooler Master2532,5001CDU · D2C · Sidecar · Manifold—Server, In-rack, In-rowWG—Asia-Pacific2026-11-09
Motivair by Schneider Electric10512,5001CDU · D2C · RDHx · SidecarNVIDIA (CDUs stated as certified for NVIDIA's latest hardware); NVIDIA NVL144 (HDU sized 1:1)Server, In-rack, In-row, FacilityWGSchneider ElectricNorth America2026-11-09
Boyd Thermal (Eaton)1512,3003CDU · D2C · Sidecar · Manifold—Server, In-rack, In-rowWGEatonEurope2026-11-09
Vertiv7012,3001CDU · Sidecar—In-rack, In-rowWG—North America2026-11-09
Airedale by Modine40022,1602CDU—In-row, FacilityWGModineEurope2026-11-09
Nidec2,00012,0001CDUNVIDIA Vera Rubin NVL72 (NIR 2.5)In-rack, In-rowWG—Asia-Pacific2026-11-09
nVent—2,0001CDU · RDHx · Manifold—In-rack, In-rowWG—Europe2026-11-09
STULZ34512,0002CDU—In-rowWG—Europe2026-11-09
ZutaCore2012,0001CDU · D2C · D2C-2φNVIDIA GB200 Grace Blackwell (ZutaCore release); AMD, Intel and NVIDIA CPUs/GPUs (general support)Server, In-rack, In-rowDE-2φ—North America2026-11-09
JetCool (Flex)30011,8001CDU · D2C · Manifold · QD—Server, In-rack, In-rowWGFlexNorth America2026-11-09
HPE (Hewlett Packard Enterprise)7541,6003CDU · D2C · OEM—Server, In-rack, In-rowWG—North America2026-11-09
Chilldyne30021,5001CDU · D2C · Manifold—Server, In-rack, In-rowWG—North America2026-11-09
Delta Electronics50021,5001CDUNVIDIA MGX rack GB200/GB300In-rack, In-rowWG—Asia-Pacific2026-11-09
Rittal15031,5002CDU—In-rack, In-rowWGFriedhelm Loh GroupEurope2026-11-09
LiquidStack1,35011,3501CDUNVIDIA Vera Rubin (GigaModular)In-row, FacilityWGTrane TechnologiesNorth America2026-11-09
Johnson Controls (Silent-Aire)50011,0501CDU—In-row, FacilityWGJohnson ControlsEurope2026-11-09
GRC (Green Revolution Cooling)1313681IMM-1φ · Fluid—In-rackDE-1φ—North America2026-11-09
Accelsius15032502CDU · D2C · D2C-2φNVIDIA H100; NVIDIA H200; NVIDIA B200; NVIDIA Grace CPU; AMD MI325X; AMD MI355XServer, In-rack, In-rowDE-2φInnventureNorth America2026-11-09
Asperitas——IMM-1φ—In-rackDE-1φ—Europe2026-11-09
AVC (Asia Vital Components)——CDU · D2C · Manifold—Server, In-rowWG—Asia-Pacific2026-11-09
Castrol——IMM-1φ · Fluid——WG · DE-1φ——2026-11-09
CEJN——QD—Server, In-rackWG · DE-1φ—Europe2026-11-09
Chemours (Opteon)——IMM-2φ · Fluid——DE-2φ—North America2026-11-09
CPC (Colder Products Company)——QD—Server, In-rackWGDoverNorth America2026-11-09
Danfoss Power Solutions (Hansen couplings)——QD—In-rack, In-row, FacilityWGDanfossEurope2026-11-09
Dell Technologies (PowerCool)——CDU · D2C · RDHx · OEMNVIDIA GB300 NVL72 (PowerEdge XE9712); NVIDIA B200 (PowerEdge XE9680L)Server, In-rackWG—North America2026-11-09
Dow——IMM-1φ · Fluid——WG · DE-1φ—North America2026-11-09
EAS Companies (Environmental Air Systems)——CDU—Facility—Comfort Systems USANorth America2026-11-09
Engineered Fluids——IMM-1φ · Fluid——DE-1φ—North America2026-11-09
Envicool——CDU · D2C · IMM-1φ · Manifold · QD—Server, In-rack, In-row, FacilityWG · DE-1φ—Asia-Pacific2026-11-09
GIGABYTE (Giga Computing)——D2C · OEMNVIDIA Vera Rubin NVL72Server, In-rack—GIGABYTE TechnologyAsia-Pacific2026-11-09
Hypertec——IMM-1φ · OEMAMD Instinct MI300AServerDE-1φ—North America2026-11-09
Iceotope——IMM-1φ—ServerDE-1φ—Europe2026-11-09
Kehua Data——CDU—In-row, FacilityWG—Asia-Pacific2026-11-09
Legrand (USystems ColdLogik)——RDHx—In-rackWGLegrandEurope2026-11-09
Lenovo Neptune——D2C · OEMNVIDIA GB300 NVL72 (Lenovo rack-scale system)Server, In-rackWGLenovoAsia-Pacific2026-11-09
Parker Hannifin——QDNVIDIA Partner Network approved (UQD)Server, In-rackWG · DE-1φ—North America2026-11-09
Shell (Immersion Cooling Fluids)——Fluid——DE-1φShell plcEurope2026-11-09
Stäubli——QD—Server, In-rack, In-rowWG—Europe2026-11-09
Submer——IMM-1φ—In-rackDE-1φ—Europe2026-11-09
TotalEnergies Fluids——IMM-1φ · Fluid——DE-1φTotalEnergiesEurope2026-11-09
Wiwynn——D2C · OEM—Server, In-rack——Asia-Pacific2026-11-09
Technologies
CDUCoolant distribution unit
D2CDirect-to-chip cold plate
D2C-2φTwo-phase direct-to-chip cold plate
IMM-1φSingle-phase immersion tank
IMM-2φTwo-phase immersion tank
RDHxRear-door heat exchanger
SidecarLiquid-to-air CDU
ManifoldRack and row manifolds
QDQuick-disconnect couplings
OEMServer maker with liquid-cooled racks
FluidCoolant fluid supplier
Coolant
WGWater-glycol
DE-1φSingle-phase dielectric
DE-2φTwo-phase dielectric or refrigerant

Ownership changes

5 deals

Largest shipping CDUs

All CDUs

How to read the numbers

Full methodology

Every kW figure is the vendor’s own rating, read from its datasheet, product page or release. The small number beside a figure opens that source with the date we read it. A blank cell means the vendor publishes no figure.

Ratings depend on the approach temperature. Rittal’s in-row CDU is 1,000 kW at 4 K and 1,500 kW at 6 K, so the table carries the conditions in each vendor’s spec notes. Compare units at the same approach before you shortlist.

Ranges cover shipping hardware only. Announced units such as Nidec’s 3.2 MW NIR 3.0 and Delta’s 2.4 MW and 3 MW in-row CDUs are named on the vendor page and kept out of the range. Featured placement is paid and labelled; every row sorts on its own ratings.

What buyers ask

What size CDUs can I buy today?

Shipping coolant distribution units run from 13 kW to 8,150 kW. At the small end sit liquid-to-air units: GRC’s ICEraQ NANO at 13 kW, Boyd’s RAA15 at 15 kW and Cooler Master’s 25 kW unit. In-rack CDUs cover 100–300 kW (Supermicro 250 kW, JetCool SmartSense 300 kW). For 17 of the 22 vendors that publish a largest CDU, it sits at 1–3 MW: Vertiv CDU 2300, Motivair up to 2.5 MW, Nidec NIR 2.5 at 2 MW and CoolIT CHx3000 at 3 MW. Above that, Carrier QuantumLeap and Supermicro’s in-row CDU reach 5 MW and DCX’s FDU V2AT2 8.15 MW.

Sources: GRC ICEraQ, Vertiv CoolChip CDU, CoolIT CDUs, DCX 8 MW FDU (Business Wire), Supermicro liquid cooling

What if my building has no facility water?

Use a liquid-to-air CDU, often called a sidecar. It rejects the heat from the cold plate loop into room air, so you can run direct-to-chip cooling without chilled-water piping. Vertiv’s CoolChip CDU 70 handles 70 kW in-row, Motivair’s HDU rejects 100 kW from a 600 mm wide cabinet, Boyd’s 10U unit does 32 kW and ZutaCore sells a 20 kW air-based CDU. Liquid-to-air units top out far below liquid-to-liquid CDUs, so they suit pilots, labs and single racks.

Sources: Schneider Electric and Motivair portfolio, Boyd 10U CDU datasheet, Vertiv CoolChip CDU

Which CDUs are built for NVIDIA GB200, GB300 and Vera Rubin racks?

CoolIT says its CHx2000 cools up to twelve 120 kW GB200 NVL72 racks and built the CHx3000 for Vera Rubin and AMD Helios. Nidec’s NIR 2.5 serves up to six Vera Rubin NVL72 racks. DCX’s 8 MW FDU runs on 45 °C warm water for GB200, GB300 and Vera Rubin. Delta cools an MGX GB200/GB300 rack at 250 kW. NVIDIA publishes no CDU supplier list, so ask each vendor for the test report at your own rating point.

Sources: DCD: CoolIT 2 MW CDU, Nidec in-row CDUs, DCX 8 MW FDU (Business Wire)

Can I run liquid cooling without chillers?

Yes, in many climates. Supermicro’s in-rack CDU runs on facility water up to 45 °C, Lenovo Neptune takes coolant up to about 45 °C, Accelsius rates the MR250 for facility water up to 45 °C and DCX built its 8 MW FDU for 45 °C. STULZ rates the CyberCool CDU at 32 °C facility water (ASHRAE W32). Warmer water lowers the rated capacity of the same unit, so compare CDUs at the same approach temperature.

Sources: Supermicro in-rack CDU datasheet, Accelsius NeuCool MR250, STULZ CyberCool CDU

Immersion or direct-to-chip: which do AI buildouts use?

Direct-to-chip is what the server makers ship: Dell, HPE, Lenovo, Supermicro, Wiwynn and GIGABYTE all sell direct-to-chip cold plates, while Hypertec builds servers for immersion, and Dell rates its IR7000 ORv3 rack at up to 504 kW with direct liquid cooling. Single-phase immersion still publishes big numbers per tank: GRC ICEraQ systems run a CDU up to 368 kW and Submer lists its SmartPod EXO at 280 kW+. Two-phase immersion lost its main fluid when 3M exited Novec; Chemours’ Opteon 2P50 replacement is still labelled developmental, and LiquidStack, a two-phase pioneer, now sells only direct-to-chip CDUs.

Sources: Dell IR7000, GRC ICEraQ, Submer SmartPod EXO, Opteon 2P50

Who owns the big liquid cooling specialists now?

Most of them changed hands in the last two years. Ecolab closed its purchase of CoolIT Systems on 2 July 2026. Eaton closed its $9.5 billion purchase of Boyd Thermal on 12 March 2026. Trane Technologies completed its acquisition of LiquidStack in March 2026. Schneider Electric holds 75% of Motivair and has the right to buy the rest in 2028. Flex has owned JetCool since November 2024 and plans to spin its cloud and power business, JetCool included, off as Axiom in early 2027. Vertiv bought CoolTera in December 2023.

Sources: Ecolab Form 10-Q, Q3 2026, Eaton completes Boyd Thermal acquisition, Trane completes LiquidStack deal, Schneider completes Motivair stake, DCD: Flex acquires JetCool, Flex 8-K: Axiom spin-off